USP and Ph EUR Purified Water and Ph EUR Highly purified Water Requirements. Triton is a unique package system integrating many features.
Overview
Features
- Cabinet design with integrated pure water storage
- State-of-the art and proven electrodeionisation module
- Internal boost and distribution pumps
- Automatic self-disinfection system
- Low noise level & minimised footprint
- Unique pharmaceutical design for pure water applications
- Assembled and tested prior shipment
Applications
- Purified water needs of 350 l/h (1.54 gpm)
- Production of clinical trial material
- Scale-up from research to production
- Pilot trials
- Small volume specialist products
- Large scale research products
Features |
Benefits |
---|---|
Integral class "A" air break tank on feedwater supply |
To comply with local by-laws and save space |
High efficiency Reverse Osmosis membrane |
For broad removal of organic/inorganics |
Chemical free electrodeionisation module |
For exceeding purified water conductivity specification |
Integral 350 ltr Triton water reservoir with bacterial vent filter to maintain microbiological integrity and spray-ball return to ensure full coverage of internal surfaces |
To prevent bio-film build up |
Variable speed re-circulation pump |
To provide instantaneous delivery flow whilst minimising temperature gain and noise level |
Ultra-violet steriliser |
For continual bacteria destruction and maintenance of low microbiological levels |
Ultrafiltration membrane (optional) |
Providing Highly Purified Water quality (with respect to bacteria and endotoxin) |
Integrated self-disinfection facility with comprehensive monitoring and control system |
To maintain the system in a hygienic state and to support validation and protect downstream processes by inhibiting bacterial growth opportunities |
Hygienic sample point |
To ensure reliable and consistent, off line water quality monitoring |
Small footprint (depth & width) |
Maximises use of space |
Product and loop return calibrated conductivity-meter |
To comply with USP <645> non-temperature compensated conductivity requirement |
State-of-the art disinfection
Access is secured by a unique 'i-button' control interface. The system recognises the disinfectant solution and the disinfection is fully automated monitoring and control. No need to remove filters or CEDI.
Maintenance
Direct access via the front-entry service door, plus quick-fit connections, facilitates easy replacement of consumables. For extra convenience and enhanced quality control, the Triton also features reminders for disinfection, maintenance and consumable replacements.
Applications
Treated Water Specification |
|
---|---|
Max.continuous make-up flowrate |
350 l/h @15ºC |
Distribution flowrate |
1800 l/h @ 3.5 bar |
Conductivity |
<1.3 µS/cm* |
Bacteria |
<100cfu/ml** |
Endotoxin |
<0.25Eu/ml*** |
*subject to a max feedwater conductivity of <700 µS/cm. For use outside the range please contact the technical department.
**System to be regularly sanitised and installed according to design guidelines. Sample to be taken from hygienic sample valve and sampled in accordance with VWS guidelines.
***Optional ultrafiltration required for endotoxin guarantee.
Feedwater Requirements |
||
---|---|---|
Hardness |
Total Hardness |
<10* |
Total Chlorine |
CI ppm |
<0.05 |
Silica |
Si02 ppm |
<5 |
Fouling Index |
FI |
<5 |
Iron/Manganese |
FE/Mn ppm |
<0.05 |
Temperature |
Recommended 15-20ºC |
|
Max flowrate |
600 l/h |
|
Drain requirements (gravity fall with air gap) max during sanitisation |
1800 l/h |
|
Feedwater pressure |
10bar (150psi) max 2bar (30psi) min |
*Requires a softened water feed as standard
Weights and Dimensions
- Height - 1820mm
- Width - 950mm
- Depth - 1100mm
- Supply weight - 250kg
- Operational weight - 600kg
Electrical Requirements
- Mains input - 400av ac, 50Hz
- Power consumption (peak demand) - 4000VA
- Electrical protection rating - 20amps
- Noise level during re-circulation - <60dBA